OK so here's the deal, the fixture mfg. Has done what is called derate or adjust for
temperature, the temperature near the ballast may be high causing the wire to get hot as well
The hotter the wire the less ampacity it can carry, so the mfg has specified 90° wire to account for the increased temp., The increased temp can also break down the insulation, this is the biggest reason to derate.
All you have to do is put the old wire in a junction box and take a short piece of new wire to the fixtures, 1 4x4 metal box, blank plate and 2 Romex connectors and some wire nuts, and your good to go.